Last Updated:2022/12/24
During scram operation, a scram signal de-energizes the inlet and outlet scram valves. The outlet scram valve vents the volume above the drive piston to a scram dump tank. The inlet scram valve supplies scram pressure obtained from an accumulator to the under side of the vented piston.